The AWA MODULA 7500 system produces up to 7500 litres per day of very high quality water.
Alongside water production for a simple system, the AWA MODULA 750 system can also be configured to integrate and complement existing HVAC (Heating, Ventilation, and Air Conditioning) systems by simultaneously producing:
- Primary Cool Air at 22°C and 40% R.H. (24,000 m3/hour)
- Cooling of water to 7°C
- Heating of external water source to 50°C up to 6000 Litres/Hour
The utilisation of the HVAC (cool air, hot water, cold water) energy produced during water production can provide substantial energy cost savings which can totally offsets the cost of water production.
The AWA MODULA 750 system can be easily installed in private homes, hotels, resorts, residential buildings, hospitals, farms, camps, communities, greenhouses, hydroponics and irrigation.
CHARACTERISTICS | AWA MODULA 750-W-X | |
---|---|---|
Nominal water production | 7500 litres/day | |
Installed electrical power | 185 kW (170 kW ± 10%) | |
Nominal environment conditions | 30° C & 70% R.H. | |
Energy consumption | 0.28 kWh/litre | |
Cooling circuit coolant | R134a | |
Sound pressure level | 79 dBA (at a distance of 10 m) | |
Size (W x D x H) | 11700 x 2230 x 2470 mm | |
Weight | 12000 kg | |
Operating range | from 5° C / 90% R.H. to 50° C/10% R.H. |
X (Model) | Power supply | |
---|---|---|
S version | 400 V + 10% / 3Ph + Ground / 50 Hz | |
A version | 460 V+ 10% / 3Ph + Ground / 60 Hz | |
L version | 220 V + 10% / 3Ph + Ground / 60 Hz |
CHARACTERISTICS | AWA MODULA 750-HWA-X | |
---|---|---|
Nominal water production | 7500 litres/day | |
Installed electrical power | 185 kW (170 kW ± 10%) | |
Nominal environment conditions | 30° C & 70% R.H. | |
Energy consumption | 0.28 kWh/litre | |
Cooling circuit coolant | R134a | |
Sound pressure level | 79 dBA (at a distance of 10 m) | |
Size (W x D x H) | 11700 x 2230 x 2470 mm | |
Weight | 12000 kg | |
Operating range | from 5° C / 90% R.H. to 50° C/10% R.H. | |
Available heating thermal power (Water) | 360 kW – 6000 litres/hour 50° C | |
Available cooling thermal power (Air) | 300 kW – 24000 m3/hour at 24° C 40% R.H. |
X (Model) | Power supply | |
---|---|---|
S version | 400 V + 10% / 3Ph + Ground / 50 Hz | |
A version | 460 V+ 10% / 3Ph + Ground / 60 Hz | |
L version | 220 V + 10% / 3Ph + Ground / 60 Hz |
CHARACTERISTICS | AWA MODULA 750-HWAC-X | |
---|---|---|
Nominal water production | 7500 litres/day | |
Installed electrical power | 185 kW (170 kW ± 10%) | |
Nominal environment conditions | 30° C & 70% R.H. | |
Energy consumption | 0.28 kWh/litre | |
Cooling circuit coolant | Environment friendly – R134a | |
Sound pressure level | 79 dBA (at a distance of 10 m) | |
Size (W x D x H) | 11700 x 2230 x 2470 mm | |
Weight | 12000 kg | |
Operating range | from 5° C / 90% R.H. to 50° C/10% R.H. | |
Available heating thermal power (Water) | 360 kW – 6000 litres/hour 50° C | |
Available cooling thermal power (Air) | 300 kW – 24000 m3/hour at 24° C 40% R.H. | |
Available cooling thermal power (Water) | From 25 to 300 kW* |
X (Model) | Power supply | |
---|---|---|
S version | 400 V + 10% / 3Ph + Ground / 50 Hz | |
A version | 460 V+ 10% / 3Ph + Ground / 60 Hz | |
L version | 220 V + 10% / 3Ph + Ground / 60 Hz |